Skip to main content
 logo

VD-SV-EB

Pressure/Vacuum Relief Valve deflagration- and endurance burning-proof

  • 10% technology for minimum pressure increase up to full lift for explosion group IIA (NEC group D) vapours
  • extreme tightness, resulting in lowest possible product losses and reduced environmental pollution
  • due to 10% technology, set pressure is close to opening pressure for optimum pressure maintenance in the system as compared to conventional 40% or 100% technology
  • valve opens later and closes earlier than conventional valves
  • valve pallet is guided inside the housing to protect against harsh weather conditions
  • can be used as a protective system in areas with potentially explosive atmospheres in accordance with ATEX
  • FLAMEFILTER® provides protection against atmospheric deflagrations and endurance burning
  • integrated PROTEGO® flame arrester unit saves space and weight and reduces costs
  • PROTEGO® flame arrester unit is protected from clogging and sticky substances caused by product vapors
  • minimum pressure loss of the PROTEGO® flame arrester unit
  • high flow capacity due to large FLAMEFILTER® cross section
  • flameproof condensate drain
  • maintenance-friendly design
  • modular design enables replacement of individual FLAMEFILTER® discs and valve pallet

Função e descrição

The deflagration-proof and endurance burning-proof VD-SV-EB type PROTEGO® valve is a highly developed combined pressure/vacuum relief valve for high flow capacities with the integrated flame arrester PROTEGO® EB. It is primarily used as a device for flame transmission-proof in-breathing and out-breathing in tanks, containers, and process equipment. The valve offers reliable protection against over pressure and vacuum, prevents out-breathing of product vapor and in-breathing of air almost up to the set pressure, and protects against atmospheric deflagration and endurance burning if stabilized burning occurs. The PROTEGO® flame arrester unit is designed to achieve minimum pressure drop with maximum safety. The deflagration-proof and endurance burning-proof PROTEGO® VD-SV-EB device is available for substances from explosion group IIA (NEC group D MESG > 0.9 mm).

When the set pressure is reached, the valve starts to open and reaches full lift within 10% overpressure. This unique 10% technology enables a set pressure that is only 10% below the maximum allowable working pressure (MAWP) of the tank.

After years of development, this typical opening characteristic of a safety relief valve is now also available for the low pressure range.

The tank pressure is maintained up to the set pressure with a tightness that is above the normal standards due to our state-of-the-art manufacturing technology. This feature is ensured by valve seats made of high quality stainless steel and with individually lapped valve pallets (1), or with an air cushion seal (2), in conjunction with a high quality FEP diaphragm. The valve pallets are also available with a PTFE seal to prevent them from sticking when sticky substances are used and to enable the use in corrosive fluids. After the overpressure is released, the valve re-seats and provides a tight seal.

If the set pressure is exceeded, explosive gas/product vapor/air mixtures are released into the atmosphere. If this mixture ignites, the integrated flame arrester PROTEGO® EB (3) prevents flame transmission into the tank. If additional mixture continues to flow and stabilized burning occurs, the integrated flame arrester unit prevents flashback as a result of endurance burning. The valve is protected and also fulfils its function under these severe conditions. The spring-loaded weather hood opens as soon as the melting element (4) melts.

The valve can be used at an operating temperature of up to +60°C / 140°F and meets the requirements of European tank design standard EN 14015 (Appendix L) and ISO 28300 (API 2000).

Type-approved in accordance with the current ATEX Directive and EN ISO 16852, as well as other international standards.

Tabela de dimensões

Para escolher o diâmetro nominal (DN), veja os diagramas de vazão nas páginas seguintes

DNDN2abcdefg
150 / 6“400 / 16“705 / 27.76844 / 33.23802 / 31.57957 / 37.68235 / 9.251500 / 59.06109 / 4.29
200 / 8“400 / 16“705 / 27.76939 / 36.97802 / 31.571027 / 40.43235 / 9.251500 / 59.06109 / 4.29
Dimensões em mm Dimensions for pressure valves with heating jacket upon request

Seleção do material do corpo

Design BC
HousingSteelStainless Steel
Heating jacket (VD-SV-EB-H-...) SteelStainless Steel
Valve seats Stainless Steel Stainless Steel
GasketPTFEPTFE
Flange ringSteel Stainless Steel
Weather hood Steel Stainless Steel
Flame arrester unitAA, B
Special materials upon request

Combinações de material do conjunto abafador de chamas

Design   AB
FLAMEFILTER® cage Steel Stainless Steel
FLAMEFILTER® Stainless Steel Stainless Steel
Safety bar Stainless Steel Stainless Steel
Special materials upon request

Seleção do material do disco da válvula de pressão

Design ABCDEF
Pressure range [mbar]
[inch W.C.]
+2.0 up to +3.5
 +0.8 up to +1.4
>+3.5 up to +14
 >+1.4 up to +5.6
>+14 up to +35
 >+5.6 up to +14
>+35 up to +60
 >+14 up to +24
>+14 up to +35
 >+5.6 up to +14
>+35 up to +60
 >+14 up to +24
Valve palletAluminiumStainless SteelStainless SteelStainless SteelStainless SteelStainless Steel
SealingFEPFEPMetal to MetalMetal to MetalPTFEPTFE
Special material as well as higher set pressure upon request

Seleção do material do disco da válvula de vácuo

Design ABCDEF
Vacuum range [mbar]
[inch W.C.]
-2.0 up to -3.5
 -0.8 up to -1.4
<-3.5 up to -14
 <-1.4 up to -5.6
<-14 up to -35
 <-5.6 up to -14
<-14 up to -35
 <-5.6 up to -14
<-35 up to -60
 <-14 up to -24
<-35 up to -60
 <-14 up to -24
Valve palletAluminiumStainless SteelStainless SteelStainless SteelStainless SteelStainless Steel
SealingFEPFEPMetal to MetalPTFEMetal to MetalPTFE
Special material as well as higher set pressure upon request

Seleção do grupo de explosão

MESGExpl. Gr. (IEC / CEN)Gas Group (NEC)
> 0,90 mmIIAD
Special approvals upon request

Tipo de conexão flangeada

EN 1092-1; Form B1
ASME B16.5 CL 150 R.F.
other types upon request

Versão e especificação

Any combination of vacuum and pressure levels can be set for the valve
The valve discs are weight-loaded.

Pressure/vacuum relief valve, basic design

VD-SV-EB - –

Pressure/vacuum relief valve, with heating jacket

VD-SV-EB - H

Outros dispositivos especiais sob solicitação

Ajustes de pressão

Pressão: +2.0 mbar +60 mbar
+0.8 inch W.C. +24 inch W.C.
Vácuo: -2.0 mbar -60 mbar
-0.8 inch W.C. -24 inch W.C.
Higher and lower settings upon request

Diagrama de vazão

Este diagrama de vazão foi determinado em uma bancada de medição de vazão calibrada e certificada pela TÜV. A vazão V em m³/h se refere ao estado técnico padrão de ar, conforme ISO 6358 (20°C, 1bar). Para conversão em outras densidades e temperaturas, veja o cap. 1: Bases técnicas.